Catalog preferences

ECOPOWER PRO CH-HP08UIMPZK-P

Wider operating range, higher efficiency
20% higher heat exchange efficiency
Quiet design: suspended frame
Quiet design: one-touch quiet mode
Quiet design: comprehensive noise reduction
Easy maintenance
Design with full water drainage

cooling 6 kW
Heating 6 kW
power consumption 3.5 W
Find out the price

Specifications

Model - - CH-HP08UIMPZK-P
Nominal Heating Capacity (А) kW 6
Heating Capacity Range - kW 1.90-6.38
Heating Power Input Range - kW 0.44-1.27
Nominal Capacity (В) kW 6
Heating Capacity Range - kW 1.06-6.72
Heating Power Input Range - kW 0.65-2.12
Nominal Cooling Capacity (С) kW 6
Cooling Capacity Range - kW 2.05-10.05
Cooling Power Input Range - kW 0.53-2.62
Nominal Cooling Capacity (D) kW 6
Cooling Capacity Range - kW 1.12-6.82
Cooling Power Input Range - kW 0.57-2.54
Max. Power Input - kW 3.5
Max. Current Input - A 15.5
Power Supply - V/ph/Hz ~220-240/1/50
Refrigerant Type - - R290
Refrigerant Volume - kg 0.7
Compressor type - - Rotary
Compressor Quantity - - 1
Fan Motor Type - - DC
Fan Quantity - - 1
Sound Pressure (1m) - dB 39
Sound Power Level (EN12102) - dB 48
Water Connection - inch 1
Rated Water Flow - m³/h 1.03
Water Pressure Drop - kPa 12
Circulation Pump Head - m 7
Operating Ambient Temperature - °C -30~45
Unit Dimensions (L/W/H)  Net mm 1370х590х915
Unit Dimensions (L/W/H)  Shipping mm 1490x610x1050
Weight  Net kg 133

Heating working condition (A): (DB/WB)7°C/6°C. Outlet water temp.35°C.
Heating working condition (B): (DB/WB)7°C/6°C. Outlet water temp.55°C.
Cooling working condition (C): (DB/WB)35°C/24°C, Outlet water temp.18°C.
Cooling working condition (D): (DB/WB)35°C/24°C, Outlet water temp.7°C.
BS EN14511-1-2013 Air conditioner, whole liquid cooling machine, electric compressor.
Part2: Test condition; Part3: Test method; Part4: Related requirements.