| Capacity |
Cold |
kW |
7.00 |
| Warm |
kW |
8.00 |
| Power supply |
~220-240V/50Hz/1Ph |
| Rated input |
Cold |
kW |
2.61 |
| Warm |
kW |
2.59 |
| Current rate |
Cold |
A |
11.80 |
| Warm |
A |
11.70 |
| Energy efficiency |
EER (Cold) |
kW/kW |
2.68 |
| C.O.P. (Warm) |
kW/kW |
3.09 |
| Air capacity |
m³/h |
1000/1080/1170 |
| Sound-pressure level |
Indoor unit |
dB(А) |
46/48/50 |
| Outdoor unit |
dB(А) |
59 |
| Refrigerant coolant type |
R410a |
| Dimensions (width/height/depth) |
Indoor unit/Outdoor unit |
mm |
1300х600х188/ 1018х695х412 |
| Weight |
Indoor unit/Outdoor unit |
kg |
33/59 |
| Refrigerant coolant |
kg |
2.2 |
| Operational temperature range |
Cold |
°C |
+18 ... +43 |
| Warm |
°C |
-7 ... +24 |
| Fluid pipeline diameter |
mm/inch |
9.53/3/8" |
| Gas pipeline diameter |
mm/inch |
15.88/5/8" |
| Maximum pipeline level difference |
m |
15 |
| Maximum pipeline length |
m |
30 |
| The distance between the mounting of the outdoor unit |
|
mm |
572 |
| Number of the interblock strands (for control) |
2*0.75 – up to 20 m long |
| Main power supply area |
Outdoor |
| Number of strands (power supply) |
Indoor unit |
|
3(Ø1.0 mm) |
| Outdoor unit |
|
3(Ø4.0 mm) |
| Factory freon fill (for the number of running meters) |
r.m. |
5 |
| Quantity of freon per one running meter (surplus. for one running meter) |
gramm/r.m. |
60 |