Capacity |
Cold |
kW |
10.00 |
Warm |
kW |
12.00 |
Power supply |
~380-415V/50РHz/3Ph |
Rated input |
Cold |
kW |
3.12 |
Warm |
kW |
3.32 |
Current rate |
Cold |
A |
5.40 |
Warm |
A |
5.80 |
Energy efficiency |
EER (Cold) |
kW/kW |
3.21 |
C.O.P. (Warm) |
kW/kW |
3.61 |
Air capacity |
m³/h |
2100 |
Nominal pressure |
Indoor unit |
Pа |
37 |
Pressure range |
Indoor unit |
Pа |
0-100 |
Sound-pressure level |
Indoor unit/Outdoor unit |
dB(А) |
53/52/48/44/63 |
Refrigerant coolant type |
R410a |
Refrigerant coolant |
kg |
3.5 |
Dimensions (width/height/depth) |
Indoor unit/Outdoor unit |
mm |
1226х775х290 / 1107х440х1100 |
Weight |
Indoor unit/Outdoor unit |
kg |
46/98 |
Operational temperature range |
Cold |
°C |
-15 ... +48 |
Warm |
°C |
-20 ... +24 |
Fluid pipeline diameter |
mm/inch |
9.53/ 3/8" |
Gas pipeline diameter |
mm/inch |
15.88/ 5/8" |
Maximum pipeline level difference |
m |
15 |
Maximum pipeline length |
m |
30 |
Number of the interblock strands (for control) |
2*1.0 – up to 20 m long |
Main power supply area |
Outdoor |
Number of strands (power supply) |
Indoor unit |
|
3(Ø1.0 mm) |
Outdoor unit |
|
3(Ø1.5 mm) |
Factory freon fill (for the number of running meters) |
r.m. |
5 |
Quantity of freon per one running meter (surplus. for one running meter) |
gramm/r.m. |
60 |
SEER/SCOP |
5.1/4.0 |