Catalog preferences

Unitherm 5 CH-HP16SIRM5 (9kw electric heater)

Find out the price

Specifications

Model _ _ CH-HP16SIRM5
(9kw electric heater)
Power Supply _ _ 400VAC, 50HZ
Capacity*1 Cooling
(floor cooling)
kW 14.90
Capacity*1 Heating
(floor heating)
kW 16.00
Power Input*1 Cooling
(floor cooling)
kW 3.80
Power Input*1 Heating
(floor heating)
kW 3.48
EER*1
(floor cooling)
_ E/W 3.60
COP*1
(floor heating)
_ w/E 4.60
Capacity*2 Cooling
(For fan coil)
kW 13.50
Capacity*2 Heating
(Fan coil or Radiator)
kE 16.00
Power Input*2 Cooling
(For fan coil)
kW 3.80
Power Input*2 Heating
(Fan coil or Radiator)
kW 4.32
EER*1
(for Fan coil)
_ W/W 2.65
COP*1
(Fan coil or Radiator)
_ W/W 3.70
Maximum current Heating A 11.20
Cooling A 9.00
Operating electrical current Heating A 6.00
Operating electrical current Cooling A 4.90
Starting current Heating A 1.90
Starting current Cooling A 1.90
Water flow rate Rated m³/h 2.67
Water flow rate Minimum m³/h 1.22
Sound pressure level Cooling dB(A) 55.4
Sound pressure level Heating dB(A) 55.4
Outdoor
dimensions
(W×D×H)
Outline mm 997×345×1352
Outdoor
dimensions
(W×D×H)
Packaged mm 1043×453×1500
Indoor
dimensions
(W×D×H)
Outline mm 429×268×935
Indoor
dimensions
(W×D×H)
Packaged mm 1138×533×340
Net weight/ Gross weight Indoor kg 51/59
Net weight/ Gross weight Outdoor kg 117/129
Connecting pipe Gas inch(mm) 5/8(16)
Connecting pipe Liquid inch(mm) 3/8(9.52)
Refrigerant charge volume kg 1.84
Operating temperature range Cooling °C -15~48
Operating temperature range Heating °C -30~35
Operating temperature range Water Heating °C -30~45